АС (ACR)

General information

Wires AC (ACR) are designed to distribute electricity over the air networks in climatic conditions related to atmospheres of types I and II specified in GOST 15150.

AC (ACR) type wires are designed for overhead power transmission in I and II type atmospheric conditions specified in GOST 15150. ACK, ACKC (ACSR), ACKП (ACSS) type wires are used on sea coasts and salt-lake coasts, in industrial cities and regions, in salt-marsh areas as well as in places with an atmosphere of types II and III.

STRUСTURAL DESIGN

  1. Aluminum wires
  2. Galvanized steel wire core

The difference of ACK wires from AC wires is the presence of a heat-resistant neutral lubricant, which protects from the heating of the steel core and one or two layers of PET tape wrapper.

The difference of ACKC wires from ACK wires is the presence of a heat-resistant neutral lubricant, which protects from the heating caused by a PET tape wrapper.

The difference of ACKП wires form other types of wires is the presence of a heat-resistant neutral lubricant on the outer layer, which protects from external heating and heating of other layers.

Technical parameters

Type of wire

Cross-section area, mm2

Breaking strength, N (min)

Estimated weight of a wire, kg/km

Maximum conductor resistance at a temperature 20 °С (max)

АС (ACR)

10/1.8

16/2.7

25/4.2

35/6.2

40/6.7

50/8.0

63/10.5

70/11

70/72

95/16

95/141

100/16.7

120/19

120/27

125/20.4

150/19

150/24

150/34

160/8.9

160/26.1

185/24

185/29

185/43

185/128

200/11.1

200/32.6

205/27

240/32

240/39

240/56

300/39

300/48

300/66

300/67

300/204

315/21.8

315/51.3

330/30

330/43

400/27.7

400/51.9

400/18

400/22

400/51

400/64

400/93

450/31.1

450/56

500/34.6

500/64.8

500/26

500/27

500/64

550/71

560/38.7

560/70.9

600/72

630/43.6

630.79.8

710/49.1

710/89.9

800/34.6

800/66.7

800/101.3

900/38.9

900/75

1000/43.2

1000/56

1120/47.3

1120/91.2

1250/53.8

1250/101.8

4089

62.20

9296

13524

14400

17112

21630

24130

96826

33369

180775

34333

41521

49465

45694

46307

52279

62643

36178

57689

58075

62055

77767

183816

44222

70134

63740

75050

80895

98253

90574

100623

117520

126270

284579

79030

106834

88848

103784

98356

123037

85600

95115

120481

129183

173715

107467

131370

119407

153.796

112548

112188

148257

166164

133736

172592

183835

150453

191772

169559

216124

167407

205433

243520

188333

226500

209259

224047

23428

283168

261750

316036

42.6

64.8

100.2

148.5

160.4

194.0

253.7

273.5

755.6

383.5

1356.5

402.5

472.1

523.3

502.7

555.3

600.9

675.7

508.3

646.6

706.2

728.4

847.6

1522.7

636.5

806.5

775.0

922.3

954.0

1107.1

1134.9

1188.7

1313.4

1325.0

2424.8

1042.6

1271.2

1151.8

1255.4

1317.3

1509.2

1199.7

1260.3

1489.6

1574.3

1852.3

1487.1

1639.7

1650.3

1883.9

1593.1

1537.1

1851.1

2075.3

1847.5

2099.1

2169.5

2077.1

2360.1

2342.7

2661.3

2477.6

2733.1

3002.8

2789.1

3072.9

3103.6

3210.1

3461.4

3814.3

3871.3

3871.3

2.7064

1.7818

1.1521

0.7774

0.7172

0.5951

0.4553

0.4218

0.4194

0.3007

0.3146

0.2868

0.2440

0.2531

0.2308

0.2046

0.2039

0.2061

0.1800

0.1803

0.1540

0.1591

0.1559

0.1543

0.1440

0.1442

0.1407

0.1182

0.1222

0.1197

0.0958

0.0978

0.1000

0.1000

0.0968

0.0917

0.0916

0.0861

0.0869

0.0722

0.0722

0.0758

0.0733

0.0733

0.0741

0.0711

0.0646

0.0666

0.0577

0.0578

0.0575

0.0600

0.0588

0.0526

0.0515

0.0516

0.0498

0.0458

0.0459

0.0406

0.0407

0.0361

0.0361

0.0361

0.0321

0.0321

0.0289

0.0288

0.0258

0.0253

0.0231

0.0231

 

TECHNICAL SPECIFICATIONS

  • Maximum authorized temperature of operation: +90 °C
  • Service life: AC - 45 years, ACK and ACKC - 10 years, ACKП - 25 years
  • Warranty period from the date of putting into operation: 4 years