H05V-R / H07V-R
General information
The wires are used for a fixed installation in electrical equipment, machines, mechanisms, machine tools as well as in lighting and power networks. The nominal operating voltage of these wires does not exceed 300-500 V and 450-750 V for alternating current electric networks and 1000 V for direct current
STRUCTURE
- Single or multi-wire twisted copper conductor
- PVC insulation
H05V-U, H07V-U - Rigid copper wire with PVC insulation
H05V-R, H07V-R - Flexible copper wire with PVC insulation
H05V-K, H07V-K - Copper wire of higher flexibility with PVC insulation
H03VH-U, H05VH-U - Wire with 2 or 3 parallel copper conductors, separation layer and PVC insulation
Technical parameters of the installation wires
Wire type | The number of conductors, pcs. | Cross sectional area of conductors, mm2 |
H05V-U, H07V-U H05V-R, H07V-R H05V-K, H07V-K H03VH-U, H05VH-U | 1 1 1 2 or 3 | 0.5 ÷ 10 0.5 ÷ 240 0.5 ÷ 240 0.75 ÷ 4.0 |
Technical indicators of wires
Wire type | Cross sectional area of conductor, mm2 | Approximate wire diameter, mm | Approximate wire weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than |
H05V-R | 0.5 0.75 1.0 | 2 2.2 2.3 | 8.5 12 14 | 39.6 25.5 21.8 |
HO7V-R | 1.5 2.5 4.0 6.0 10 16 25 35 50 70 95 120 150 185 240 | 3.0 3.6 4.2 4.8 5.9 6.9 8.2 9.3 10.8 12.4 14.5 15.9 17.7 19.8 22.8 | 20.6 44.4 46.8 66.3 109.8 172.2 264.5 364.3 515.1 689.0 958.5 1175 1575 1945 2520 | 14.0 7.49 4.79 3.11 1.99 1.21 0.809 0.551 0.394 0.277 0.203 0.153 0.124 0.0996 0.0754 |
Cables of other sizes are produced at the STP Cable Factory as well
TECHNICAL SPECIFICATIONS
- Maximum permissible operating temperature: + 70 °C
- Relative air humidity: 100 %
- Service time: 15 years