General information
Control cables of these brands are used in stationary electric and alternate current devices with a nominal voltage of 660V or in direct current electric distribution devices with a nominal voltage up to 1000V, in closed areas, channels and tunnels, aggressive climatic conditions and in places that are not exposed to external mechanical influence.
КВВГ (NYY) / КВВГнг (NYY-fl) / КВВГнг–LS (NYY-LS) / АКВВГ(NAYY) / АКВВГнг (NAYY-fl) / АКВВГнг – LS (NAYY-LS)
Control cables of these brands are used in stationary electric and alternate current devices with a nominal voltage of 660 V or in direct current electric distribution devices with a nominal voltage up to 1000 V, in closed areas, channels and tunnels, aggressive climatic conditions and in places that are not exposed to external mechanical influence. The cores forming the cable get twisted in layers. Two cores in each layer should differ in color between themselves and other cores or must be numbered.
Construction design:
- The power core made of copper and aluminum wire
- PVC insulation or flame retardant PVC with low smoke and gas emission
- Belt insulation from PET tape
- PVC jacket or flame retardant PVC with low smoke and gas emission
Technical characteristics of the cable:
Wire | Conductor cross-sectional area, mm2 | Estimated weight of the wire, kg/km | Maximum electrical resistance of the power core at 20 °С, Оhm/km, not more than |
KBBГ (NYY) | 4 x 1.0 5 x 1.0 7 x 1.0 10 x 1.0 14 x 1.0 19 x 1.0 27 x 1.0 37 x 1.0 | 85.3 112.5 142.0 196.0 255.1 329.2 451.7 610.7 | 18.10 |
4 x 1.5 5 x 1.5 7 x 1.5 10 x 1.5 14 x 1.5 19 x 1.5 27 x 1.5 37 x 1.5 | 118.0 141.7 182.7 253.4 332.2 432.3 612.0 809.3 | 12.10 | |
4 x 2.5 5 x 2.5 7 x 2.5 10 x 2.5 14 x 2.5 19 x 2.5 27 x 2.5 37 x 2.5 | 164.3 197.6 259.0 362.1 481.4 632.4 896.7 1214.5 | 7.41 | |
4 x 4.0 7 x 4.0 10 x 4.0 | 238.1 383.1 538.1 | 4.61 | |
4 x 6.0 7 x 6.0 10 x 6.0 | 323.5 528.3 761.1 | 3.08 |
Technical specifications:
- Nominal operating voltage: 660 V
- Conductor cross-section, mm2: 0.75, 1.0, 1.5, 2.5, 4.0, 6.0, 10.0
- Number of cores: 2 to 61
- Relative humidity of the atmosphere: 98 %
- Operating temperature of the cable: -50 °C / +50 °C
- Service life: under the ground and on the bridges - 15 years, in closed areas, canals and tunnels - 25 years