КВВГЭ (NYCY)

General information

Control cables of these brands are used for stationary laying in electric and alternate current devices with a nominal voltage of 660 V or in direct current electric distribution devices with a nominal voltage up to 1000 V, in closed areas, channels and tunnels, aggressive climatic conditions and in places that are not exposed to external mechanical influence, and also for the purpose of protection from the external electromagnetic field.

КВВГЭ (NYCY) / КВВГЭнг (NYCY-fl) / КВВГЭнг – LS (NYCY-LS) / AКВВГЭ (NAYCY) / AКВВГЭнг (NAYCY-fl) / AКВВГЭнг – LS (NAYCY-LS)

Control cables of these brands are used for stationary laying in electric and alternate current devices with a nominal voltage of 660 V or in direct current electric distribution devices with a nominal voltage up to 1000 V, in closed areas, channels and tunnels, aggressive climatic conditions and in places that are not exposed to external mechanical influence, and also for the purpose of protection from the external electromagnetic field.

The cores forming the cable are twisted in layers. Two cores in each layer should differ in color between themselves and other cores or must be numbered.

Structural design:

  1. The power core made of copper and aluminum wire
  2. PVC insulation or flame retardant PVC with low smoke and gas emission
  3. Belt insulation from PVC or PET tape
  4. Aluminum tape screen (foil)
  5. Copper wore located under the screen
  6. PVC jacket or flame retardant PVC with low smoke and gas emission

Technical characteristics of the cable:

Wire
type

Conductor cross-sectional area, mm2

Estimated weight of the wire, kg/km

Maximum electrical resistance of the power core at 20 °С, Оhm/km, not more than

КВВГЭ (NYCY)

4 x 1.0

5 x 1.0

7 x 1.0

10 x 1.0

14 x 1.0

19 x 1.0

27 x 1.0

37 x 1.0

116.3

135.0

166.8

225.5

285.8

362.7

505.8

655.4

18.10

4 x 1.5

5 x 1.5

7 x 1.5

10 x 1.5

14 x 1.5

19 x 1.5

27 x 1.5

37 x 1.5

141.3

165.5

208.1

283.9

365.2

468.4

655.8

857.6

12.10

4 x 2.5

5 x 2.5

7 x 2.5

10 x 2.5

14 x 2.5

19 x 2.5

27 x 2.5

37 x 2.5

188.4

223.6

286.9

395.9

518.0

688.2

945.6

1270.4

7.41

4 x 4.0

7 x 4.0

10 x 4.0

265.7

415.0

593.2

4.61

4 x 6.0

7 x 6.0

353.5

563.6

3.08

 

Technical specifications:

  • Nominal operating voltage: 660 V
  • Conductor cross-section, mm2: 0.75, 1.0, 1.5, 2.5, 4.0, 6.0, 10.0
  • Number of cores: 2 to 61
  • Relative humidity of the atmosphere: 98 %
  • Operating temperature of the cable: -50 °C / +50 °C
  • Service life: under the ground and on the bridges - 15 years, in closed areas, canals and tunnels - 25 years