МГ (ACC)

General information

Wires are used in electrical systems and devices, antennas.

CONSTRUCTION

Electrical conductor – copper wire stranded (in accordance with IEC 60228, V class or higher)

Table 1

Nominal cross-section area of wire, mm2

Breaking strength,
Н, min

1.5

560

2.5

960

4.0

1510

6.0

2100

10.0

3920

Table 2

Type of wire

Nominal cross-section area, mm2

Total weight of wire, kg/km

Specific electrical resistance of the conductor at a temperature of 20 °С, Ohm/km, max

МГ (ACC)

1.5

2.5

4.0

6.0

10

16

25

35

50

70

95

120

13.8

22.6

35.6

53.3

87.1

143.4

224.0

319.1

453.5

621.4

866.2

1094.1

13.3

7.98

4.95

3.30

1.91

1.21

0.78

0.554

0.386

0.272

0.206

0.161

TECHNICAL SPECIFICATIONS

  • Temperature range during operation: -60 °C / +55 °C
  • The wires are resistant to dew formation, frost, rain, sea fog, sun radiation, sand, mold fungi
  • Breaking strength of wires with a cross-section of 1.5 + 10 mm2 for antennas corresponds to data in Table 1.