NA2ХY / NA2ХY-fl / NA2ХY-LS
General information
TECHNICAL SPECIFICATIONS:
- Rated operating voltage: 0.6/1.0 kV
- The number of conductors: 1, 2, 3, 4, 5
- Permissible heating temperature of the cable conductor during operation: +90 °C
- Maximum temperature in case of short circuit: +160 °C
- Relative air humidity: 98 %
- Minimum curvature radius: 15D (outer cable diameter)
Cable specifications
Cable type | Cross-sectional area of conductor, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than |
NA2ХY / NA2ХY-fl / NA2ХY-LS 1.0 kV | 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 | 9 10.5 11.5 13 15 17 19 21 23 26 | 120 174 213 277 355 476 568 697 847 1075 | 1.910 1.200 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 |
Cable Specifications
Cable type | Cross-sectional area of conductor, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than | ||||
NA2ХY / NA2ХY-fl / NA2ХY-LS 1.0 kV | 2x16 2x25 2x35 2x50 3x16 3x25 3x35 3x50 3x70 3x95 3x120 3x150 3x185 3x240 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 4x185 4x240 5x16 5x25 5x35 3x16/16 3x25/16 3x35/16 3x50/25 3x70/35 3x95/50 3x120/70 3x150/70 3x185/95 3x240/120 | 17.8 22.2 24.6 28.6 18.9 23.6 26.2 30.5 34.0 39.5 42.9 47.7 52.9 60.2 21.0 26.1 29.0 33.8 37.8 43.8 47.7 54.0 59.7 68.0 25.2 31.8 35.4 21.0 25.0 27.6 32.4 36.0 41.7 45.9 50.1 56.2 63.3 | 450 684 843 1135 583 769 951 1277 1640 2209 2610 3241 3966 5100 635 947 1172 1572 2039 2730 3245 4165 5065 6526 990 1423 1767 635 868 1071 1436 1827 2436 3976 3482 4423 5612 | 1.910 1.200 0.868 0.641 1.910 1.200 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 1.910 1.200 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 1.910 1.200 0.868 1.91/1.91 1.20/1.91 0.868/1.91 0.641/1.20 0.443/0.868 0.320/0.641 0.253/0.443 0.206/0.443 0.164/0.320 0.125/0.253 |