NAYY / NAYY-fl / NAYY-LS
General information
Cables with rated voltages up to 0.66; , 1.0; , 3,.0 kV are used for transmission and distribution of electric energy at manufacturing entities with low and high humidity, on special cable racks, in blocks of residential buildings, in the open air, at rivers and lakes located at an altitude of up to 4,300 m above sea level. The use of these cables in trenches (under the ground) is not recommended.
STRUCTURE
- A twisted round or shaped electric copper or aluminum single- or multi-wire conductor
- PVC or SPE insulation
- PVC shell
Manufacture of electrical conductors
Type of conductors according to the number of wires forming them | Cross-section, mm2 Round / Shaped |
Single-wire | 1.5 ÷ 10 / - |
Multi-wire | 16 ÷ 240 / 25 ÷ 185 |
Cable specifications
Cable type | Cross-sectional area of conductor, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than |
YY / NAYY-fl / NAYY-LS 1.0 kV | 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 | 10 11 12 14 16 18 19 21 24 26 30 33 | 119 162 199 263 336 447 533 662 807 1013 1250 1650 | 1.91 1.20 0.87 0.64 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 |
Cable specifications
Cable type | Cross-sectional area of conductor, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than | ||||
NAYY / NAYY-fl / NAYY-LS 1,0 kV | 2x16 2x25 2x35 2x50 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 4 x 2.5 4 x 4.0 4 x 6.0 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x185 4 x 240 5 x 2.5 5 x 4.0 5 x 6.0 5 х 10 5 х 16 5 х 25 5 х 35 | 17.8 22.2 24.6 28.6 20 23 25 29 33 38 41 45 50 56 11 12 14 15 18 21 25 28 32 36 42 45 51 56 63 12 13 15 16 20 24 28 31 | 450 684 843 1135 485 681 870 1148 1512 1976 2324 2961 3552 4439 167 236 286 396 569 826 1029 1365 1828 2358 2812 3542 4255 5322 192 271 332 475 662 963 1206 | 1.91 1.20 0.87 0.64 1.91 1.20 0.87 0.64 0.443 0.320 0.253 0.206 0.164 0.125 12.4 7.41 5.11 3.08 1.91 1.20 0.87 0.64 0.443 0.320 0.253 0.206 0.164 0.125 12.4 7.41 5.11 1.91 1.20 0.87 |
Cable specifications
Cable type | Cross-sectional area of conductor, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than | ||||
NAYY / NAYY-fl / NAYY-LS 1.0 kV | 3 х 4+1 х 2.5 3 х 6+1 х 4.0 3 х 10+1 х 6.0 3 х 16+1 х 10 3 х 25+1 х 16 3 х 35+1 х 16 3 х 50+1 х 25 3 х 70+1 х 35 3 х 95+1 х 50 3 х 120+1 х 70 3 х 150+1 х 70 3 х 185+1 х 95 3 х 240+1 х 120 | 13 14 17 20 23 26 29 34 39 42 47 52 58 | 208.4 251.4 347.8 501.0 702.3 895.7 1211.4 1263.3 2048.9 2070.0 2882.8 3686.5 4604.1 | 7.41/12.4 5.11/7.41 3.08/5.11 1.91/3.08 1.2/1.91 0.87/1.2 0.64/0.87 0.443/0.64 0.320/443 0.253/0.320 0.206/0.253 0.164/0.206 0.125/0.164 |
TECHNICAL SPECIFICATIONS:
- Rated operating voltage: 0.6/1.0 kV
- The number of conductors: 1, 2, 3, 4, 5
- Permissible heating temperature of the cable conductor during operation: +70 °C
- Maximum temperature in case of short circuit: +160 °C
- Relative air humidity: 98 %
- Minimum curvature radius: 15D (outer cable diameter)