NYY FLEX / NYY-fl FLEX / NYY-LS FLEX
General information
Cable specifications
Cable type | Cross-sectional area of conductor, mm2 | Approximate cable diameter, mm | Calculated cable weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than |
NYY FLEX / NYY-fl FLEX / NYY-LS FLEX 1.0 kV | 2x6 2x10 2x16 2x25 2x35 2x50 2x70 3x6 3x10 3x16 3x25 3x35 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x16+10 3x25+16 3x35+16 3x50+25 3x70+35 3x95+50 3x120+70 3x150+70 3x185+95 3x240+120 4x6 4x10 4x16 4x25 4x35 4x50 4x70 4x95 4x120 4x150 5x4 5x6 5x10 5x16 5x25 5x35 5x50 5x70 5x95 5x150 | 12.2 15.8 18.0 23.7 25.7 30.1 33.7 13.0 16.8 20.7 24.4 27.1 31.4 35.2 41.2 43.6 48.3 55.4 61.7 21.9 25.8 28.1 32.8 36.8 42.5 46.2 50.4 58.1 64.5 15.8 20.0 22.5 26.8 30.1 34.8 39.2 45.4 48.3 53.3 16.0 17.4 20.6 25.2 29.9 33.0 38.9 44.9 50.8 59.7 | 250 424 588 1019 1269 1777 2302 305 515 851 1221 1602 2210 2909 3932 4733 5841 7317 9340 981 1421 1757 2493 3295 4396 5489 6583 8336 10625 423 764 1047 1526 2038 2801 3717 4967 6032 7412 469 597 890 1317 1909 2491 3542 4782 6602 9507 | 3.30 1.91 1.21 0.780 0.554 0.386 0.272 3.30 1.91 1.21 0.780 0.554 0.386 0.272 0.206 0.161 0.129 0.106 0.0801 1.21/1.91 0.780/1.21 0.554/1.21 0.386/0.780 0.272/0.554 0.206/0.386 0.161/0.272 0.129/0.272 0.106/0.206 0.0801/0.161 3.30 1.91 1.21 0.780 0.554 0.386 0.272 0.206 0.161 0.129 4.95 3.30 1.91 1.21 0.780 0.554 0.386 0.272 0.206 0.129 |
Low voltage power cables of other sizes are manufactured at the STP cable factory as well.