NYY / NYY-fl / NYY-LS
General information
Cables with rated voltages up to 0..66,; 1.0,; 3.,0 kV are used for transmission and distribution of electric energy at manufacturing entities with low and high humidity, on special cable racks, in blocks of residential buildings, in the open air, at rivers and lakes located at an altitude of up to 4,300 m above sea level. The use of these cables in trenches (under the ground) is not recommended.
STRUCTURE
- A twisted round or shaped electric copper or aluminum single- or multi-wire conductor
- PVC or SPE insulation
- PVC shell
Manufacture of electrical conductors
Type of conductors according to the number of wires forming them | Cross-section, mm2 |
Single-wire | 1.5 ÷ 10 / - |
Multi-wire | 16 ÷ 240 / 25 ÷ 185 |
Cable specifications
Cable type | Cross-sectional area of conductor, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than |
Y / NYY-fl / NYY-LS 1,0 kV | 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 | 8.5 95 11 12 13.5 15 17.5 19.5 21 23 26.5 29 35 | 158 212 309 404 542 738 1010 1245 1528 1907 2464 3050 4100 | 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 |
Cable specifications
Cable type | Cross-sectional area of conductor, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than |
NYY / NYY-fl / NYY-LS 1,0 kV | 2 x 1.5 2 x 2.5 2 x 4.0 2 x 6.0 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 3 x 1.5 3 x 2.5 3 x 4.0 3 x 6.0 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3 x 240 4 x 1.5 4 x 2.5 4 x 4.0 4 x 6.0 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95 4 x 120 4 x 150 4 x 185 4 x 240 5 x 1.5 5 x 2.5 5 x 4.0 5 x 6.0 5 x 10 5 x 16 5 x 25 5 x 35 | 9.5 10.5 12 13 16 18 22 24 27 10 11 13 14 17 20 23 25 29 33 38 41 45 50 56 11 12 14 15 18 21 25 28 32 36 42 45 51 56 63 12 13 15 16 20 24 28 31 | 148 183 256 317 448 646 926 1197 1616 167 211 299 378 543 794 1155 1508 2067 2812 3767 4545 5786 7074 8992 195 248 357 456 662 977 1431 1881 2600 3542 4753 5705 7348.5 8967.0 11409.6 225.0 288.9 419.0 540.4 787.9 1170.5 1721.9 2281.7 | 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 12.1 7.28 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 12.10 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 12.10 7.27 4.61 3.08 1.83 1.15 0.727 0.524 |
Cable specifications
Cable type | Cross-sectional area of conductor, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of conductor at 20 °С, Ohm/km, not more than |
NYY / NYY-fl / NYY-LS 1,0 kV | 3 x 4+1 x 2.5 3 x 6+1 x 4.0 3 x 10+1 x 6.0 3 x 16+1 x 10 3 x 25+1 x 16 3 x 35+1 x 16 3 x 50+1 x 25 3 x 70+1 x 35 3 x 95+1 x 50 3 x 120+1 x 70 3 x 150+1 x 70 3 x 185+1 x 95 3 x 240+1 x 120 | 13 14 17 20 23 26 29 34 39 42 47 52 58 | 320 388 408 869 1274 1631 2256 3091 4143 5058 6129 7787 9876 | 4.61/7.41 3.08/4.61 1.83/3.08 1.15/1.83 0.727/1.15 0.514/1.15 0.387/0.727 0.268/0.524 0.193/0.387 0.153/0.268 0.124/0.268 0.0991/0.193 0.0754/0.153 |
TECHNICAL SPECIFICATIONS:
- Rated operating voltage: 0.6/1.0 kV
- The number of conductors: 1, 2, 3, 4, 5
- Permissible heating temperature of the cable conductor during operation: +70 °C
- Maximum temperature in case of short circuit: +160 °C
- Relative air humidity: 98 %
- Minimum curvature radius: 15D (outer cable diameter)