СИП - 4 (ABC)
General information
Wire SIW-4 (ABC) is designed for overhead transmission lines with 0.66, 1.0, 10, 20, 35 kV, for input tapping of branch power lines, for in-air-laying on walls of buildings or engineering structures of types II and III according to GOST 15150. At a specified temperature of storage and operation wire materials do not give off pollutant emissions in concentrations dangerous for human body and polluting the environment.
STRUCTURAL DESIGN
- Conductor – aluminum, round, multi-wire stranded, compacted (GOST 22483 II class)
- Insulation
In SIW-4 wires, cross-linked polyethylene (XLPE) is used as an insulating material.
Technical Parameters
Type of wire | Nominal cross-sectional area, mm2 | Rated cable weight, kg/km | Specific electrical resistance of the conductor at a temperature of 20 °С, Ohm/km, max |
СИП - 4 (ABC) | 2 х 16 3 х 16 4 х 16 | 132.2 198.44 264.6 | 1.910 |
2 х 25 3 х 25 4 х 25 | 190.7 286.1 381.5 | 1.200 | |
2 х 35 3 х 35 4 х 35 | 249.7 374.5 499.3 | 0.868 | |
2 х 50 3 х 50 4 х 50 | 350.0 525.1 700.1 | 0.641 | |
4 х 70 | 978.6 | 0.443 | |
4 х 95 | 1295.1 | 0.320 | |
4 х 120 | 1571.0 | 0.253 |
TECHNICAL SPECIFICATIONS
- Rated voltage: 0.66/1.0 kV (SIW-4)
- Rated voltage: 10/20/35 kV (SIW-3)
- Nominal cross-sectional area, mm2: 16 ÷ 240 (SIW-4); mm2: 35 ÷ 240 (SIW-3)
- Wire is resistant to solar radiation
- Wire is resistant to rain
- Temperature range during operation: -60 °C / +50 °C
- Service life: 40 years
- Warranty period from the date of commissioning: 3 years
The STP cable plant produces overhead power line wires and wires of other sizes as well.